GambleLittrell713

Från Wiki
Hoppa till: navigering, sök

Charger : in a number of UPS systems as a result of nature of their design a different battery charger is used, this is more common on sub 60kVA UPS systems and is very common on small sub 3kVA products.

Battery : this is the energy storage area and is kept charged eith...

Rectifier : this part of the UPS charging current for the battery and also the supply needs for the inverter and can converts the incoming alternating current (ac) supply to direct current (dc).

Charger : in several UPS systems as a result of character of these design another battery charger is used, this is more common on sub 60kVA UPS systems and is very common on small sub 3kVA products.

Battery : here is the energy storage section and is kept charged both by the rectifier or perhaps a separate charger. As AH (ampere hour), which will be the amount of amperes of current that the battery can supply for an hour, Its storage capacity is usually exhibited. There will be an amount of limiting facets dependant on the application, generally if the design calls for a small autonomy (period of time the battery will support its weight for), the batteries may be cleared to a level, in the case of emergency lighting where there's a necessity for a autonomy the battery will not be allowed to release so far. These conditions help to enable the maximum design life of the battery to be achieved.

Inverter : an ac output is provided by this section of the Uninterruptible power supply to the weight that is in phase with the input mains supply. Due to the amount of conversions (ac to dc to ac) and the filter involved it may be referred to as a 'clean supply.'

Fixed Switch : this world can be as easy as an exchange or even more commonly using thyristors, its purpose would be to change the load between the power mains supply and the inverter. As has been mentioned before the result of the inverter is in phase with the electricity mains offer to ensure that any switching between the two is likely to be nearly seamless. This arrangement ensures that if the inverter experiences an overload condition, because fast over-current recognition tracks it'll shift the load to the more strong mains supply. A normal example would be each time a host tray is switched on, the inrush current, based upon the size of your uninterruptible power supplies, could cause the transfer to the utility mains offer, and once switched on the load will transfer back to the inverter offering the inverter has sufficient capacity to support the load. Also a problem on the inverter can cause the load to be moved, again essentially seamlessly; it would be unusual for just about any loss of load to happen during these conditions.

Preservation Bypass : more generally found in UPS systems with a capacity of 6kVA or greater. The load is allowed by this arrangement to be moved under controlled conditions to the utility mains and the UPS to be turn off without damage. Usually carried out for routine UPS maintenance or UPS fix.

External Maintenance Bypass : the installing an maintenance bypass can allow the UPS to be removed/replaced without disturbance to the load, also, if the actual maintenance bypass is fed from a different source it can allow load testing in the case of a major UPS restoration and/or checking of the independence under simulated load conditions while the site load is being supported by the external maintenance bypass circuit. When letting the UPS System to be bypassed onto standby diesel generator power this is used. Instead, when batteries are removed and changed, it could only be done by setting the uniterruptible power supply into additional bypass. discount acrow props sizes

Personliga verktyg